Connecting the trandsducer
To connect a 0-10V current transducer to an analogue input, you will need the following:
- A current transducer that is compatible with the current range being measured and output of 0-10V DC.
- An Evocon device with a free input 3.
- Wiring and a male 4-pin M12 connector.
Most commonly used CTs for Evocon are rated at 25A/0-10V or 50A/0-10V.

Input 3 has the same "mapping" for both digital and analogue modes.
- Pin 1 - Brown - +24V from device. Not connected.
- Pin 2 - White - Not connected.
- Pin 3 - Blue - 0V of the device power supply.
- Pin 4 - Black - Input. On input 3 works as an Analog input (0-10V).

Transducers can have different markings for the terminals.
For the one in the picture above, we have l and k terminals.